Thank you for taking an interest in part number 96996A8, a Spd Electrical Systems Inc product we have in stock that is listed alongside the NSN 5925008001481 and the description “Circuitbreaker.” As part number 96996A8 is readily available for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with important information such as your target price and expected shipping time frame so that we can best tailor a solution that caters to your unique needs and restrictions alike.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that you only procure the exact items you require for carrying out operations, we list all aerospace parts, military and defense parts, and other product offerings with all applicable information for identification. For example, part number 96996A8 is listed alongside the NSN 5925-00-800-1481, meaning that it also belongs to FSC 5925 Circuit Breakers. Furthermore, this NSN part is specifically manufactured under CAGE Code 30086, a unique identifier belonging to the manufacturer for a specific facility. With all of this in mind, kick off purchasing with us today and see why so many customers steadily choose us for their operational needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-800-1481 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008001481 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
96996A8 | 6 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 100000.0 AC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 90.000 MINIMUM AND 540.000 MAXIMUM ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
TTQY | TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT,FEMALE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC AND 40.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.250 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT AND 102.000 MAXIMUM AT 200 PCT AND 10.000 MINIMUM AT 300 PCT AND 28.000 MAXIMUM AT 300 PCT AND 6.000 MINIMUM AT 400 PCT AND 14.000 MAXIMUM AT 400 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |