Thank you for taking an interest in part number KAL36125, a Schneider Electric Gmbh product we have in stock that is listed alongside the NSN 5925002084081 and the description “Circuit Breaker.” As part number KAL36125 is readily available for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with important information such as your target price and expected shipping time frame so that we can best tailor a solution that caters to your unique needs and restrictions alike.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that you only procure the exact items you require for carrying out operations, we list all aerospace parts, military and defense parts, and other product offerings with all applicable information for identification. For example, part number KAL36125 is listed alongside the NSN 5925-00-208-4081, meaning that it also belongs to FSC 5925 Circuit Breakers. Furthermore, this NSN part is specifically manufactured under CAGE Code 56365, a unique identifier belonging to the manufacturer for a specific facility. With all of this in mind, kick off purchasing with us today and see why so many customers steadily choose us for their operational needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-208-4081 Item Description: Circuit Breaker | 5925 | 002084081 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Kal36125 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
MRC | Decoded Requirement | Clear Text Reply |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 7.125 INCHES NOMINAL |
AKPX | Pole Quantity | 3 |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 600.0 AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 30000.0 AC ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 138.0 ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.500 INCHES NOMINAL |
CRCF | Trip Release Ambient Temp Rating | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
AJEC | Boss Height | 0.125 INCHES NOMINAL |
CPRQ | Reset Method | MANUAL |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRX | Actuator Position Designation | AT POLE TWO |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
ADTV | Case Material | PLASTIC |
ADAT | Body Width | 4.500 INCHES NOMINAL |
ADAQ | Body Length | 8.000 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 6.562 INCHES NOMINAL |
ADAU | Body Height | 3.500 INCHES NOMINAL |
CPLM | Maximum Continuous Load Current Rating Per Pole | 125.0 AMPERES AC ALL LOCATIONS |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.500 INCHES NOMINAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 150.000 MINIMUM AT 200 PCT AND |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 275.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.201 INCHES NOMINAL |
CPRW | Actuator Function | TRIP-RESET |
TTQY | Terminal Type And Quantity | 6 COMPRESSION |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.
Request for Quote