Thank you for taking an interest in part number NJL631225, a Federal Pacific Electric Co product we have in stock that is listed alongside the NSN 5925008379417 and the description “Circuitbreaker.” As part number NJL631225 is readily available for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with important information such as your target price and expected shipping time frame so that we can best tailor a solution that caters to your unique needs and restrictions alike.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that you only procure the exact items you require for carrying out operations, we list all aerospace parts, military and defense parts, and other product offerings with all applicable information for identification. For example, part number NJL631225 is listed alongside the NSN 5925-00-837-9417, meaning that it also belongs to FSC 5925 Circuit Breakers. Furthermore, this NSN part is specifically manufactured under CAGE Code 79443, a unique identifier belonging to the manufacturer for a specific facility. With all of this in mind, kick off purchasing with us today and see why so many customers steadily choose us for their operational needs.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-837-9417 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008379417 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
J3225A | 5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.312 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.880 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 20000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 150 PCT AND 2000.000 MAXIMUM AT 150 PCT ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
ADAQ | BODY LENGTH | 6.310 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.380 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.250 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.380 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 225.0 AMPERES AC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CWJK | CASE MATERIAL | PLASTIC |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.
Request for Quote