Item Name | Circuit Breaker |
Federal Supply Group (FSG) | Electrical and Electronic Equipment Components |
Federal Supply Class (FSC) | 5925 Circuit Breakers |
National Item Identification Number (NIIN) | 01-181-7283 (011817283) |
NCB Code | USA (01) |
Manufacturer | Porta Kamp Construction Inc, Federal Specifications |
Part Number | Manufacturer | Item Name | Cage Code | RFQ |
---|---|---|---|---|
TEB132060WL | porta kamp construction inc | circuit breaker | 23644 | RFQ |
W-C-375 12 | federal specifications | circuit breaker | 81348 | RFQ |
WC375 12-010 | federal specifications | circuit breaker | 81348 | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.310 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.105 INCHES MINIMUM AND 4.125 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 3.380 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.250 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.880 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.380 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE AND 2 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 6.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTING G |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/12 GOVERNMENT SPECIFICATION |
Relevant Components for NSN - 5925-01-181-7283, 5925011817283 | ||||
5960-00-188-0930 (5960001880930) | 5905-01-265-9950 (5905012659950) | 5995-01-379-1584 (5995013791584) | 5962-01-243-3066 (5962012433066) | |
5995-01-565-3889 (5995015653889) | 5985-00-438-3422 (5985004383422) | 5995-01-570-5082 (5995015705082) | 5935-01-232-5654 (5935012325654) | |
5935-00-925-1739 (5935009251739) | 5985-01-314-9148 (5985013149148) | 5998-01-280-1852 (5998012801852) | 5935-01-310-6114 (5935013106114) | |